User Manual
Table Of Contents
- toc
- RBS Product Description
- 1 Introduction
- 2 Product Overview
- 3 Dimensions
- 4 Space Requirements
- 5 Environment
- 6 Hardware Units
- 7 Interfaces
- 7.1 External Connections
- 7.2 Test Interface
- 7.3 Operator Interface
- Figure 18 Power System
- 8.1 Power Supply
- 8.2 Battery Backup
- 8.3 Output Power to TM
- 8.4 Power Consumption
- 9 Transmission
- 10 External Alarms
- 11 Standards, Regulations and Dependability
- RBS Product Description
- tables
- Table 1 RBS Weights with Combined Climate Unit
- Table 2 RBS Weights with Heat Exchanger Climate Unit
- Table 3 RBS 2106 Colours
- Table 4 RBS 2106 Climatic Requirements
- Table 5 RBS 2106i and RBS 2106 V3 Climatic Requirements
- Table 6 Sound Pressure Level, Bystander Position without Sound H
- Table 7 Sound Pressure Level, Bystander Position with Sound Hood
- Table 8 Sound Pressure Levels for a Free Standing RBS with Combi
- Table 9 Sound Pressure Levels for an RBS against a Wall, with Co
- Table 10 Sound Pressure Level, Bystander Position without Sound
- Table 11 Sound Pressure Level, Bystander Position with Sound Hoo
- Table 12 Sound Pressure Levels for a Free Standing RBS€2106 with
- Table 13 Sound Pressure Levels for an RBS€2106 Against a Wall, w
- Table 14 Sound Pressure Level, Bystander Position without Sound
- Table 15 Sound Pressure Levels for a Free Standing RBS 2106i or
- Table 16 Sound Pressure Levels for an RBS 2106i or RBS€2106€V3 w
- Table 17 Compliance Boundary Dimensions for the General Public (
- Table 18 Characteristics of Typical Antenna
- Table 19 Maximum Power to Antenna for Various RBS€2106 Configura
- Table 20 Maximum Dimensions
- Table 21 Power Distribution for the TM Space
- Table 22 Connection Field Inlets in RBS 2106i and RBS 2106 V3
- Table 23 OVP Module Capacity
- Table 24 Overvoltage Arrestors
- Table 25 Antenna Connections
- Table 26 External Connections
- Table 27 Optical Indicators
- Table 28 Switches and Circuit Breakers
- Table 29 Power Parameters
- Table 30 Mains Fuses Recommendation
- Table 31 Output Power
- Table 32 Maximum Power Consumption during Battery Charging
Ericsson Internal
DESCRIPTION 44 ( 50 )
/ XSNSIXI 129/1551-LZA 701 0001 Uen
CBC/ XRX/M ( Kai Lian) 2011-05-05 F
Prepared (also subject responsible if other) No.
Approved Checked Date Rev Reference
8.1 Power Supply
This section describes the AC mains power supply, the external earth fault
circuit breakers, and the mains fuses.
AC Mains Supply Voltage
Single-phase, two-phase, or three-phase AC can be used.
Table 29 Power Parameters
Parametre Value
Nominal voltage 200 – 250 V AC
Operating voltage 180 – 275 V AC
Nominal frequency 50 – 60 Hz
Operating frequency 45 – 65 Hz
Maximum inrush current (total, all
phases)
60 A for 10 ms (typical duration)
PSU capacity For RBS 2106 and RBS 2106i: 4 ×
1200 W (4800 W total)
For RBS 2106 V3: 4× 1500 W (6000
W total)
BFU 1 × 200 A
BFU-32 1 × 300 A
External Earth Fault Circuit Breakers
If external earth fault (ground fault) circuit breakers are used, then the
recommended minimum trip value is 100 mA.
Mains Fuses
Table 30 Mains Fuses Recommendation
Minimum for Safe
Function
Recommended for
Maximum Selectivity
Maximum Allowed
Fuse Rating
25 A/40 A
(1)
32 A/50 A
(1)
63 A
(1) Three-phase/Single phase.
8.2 Battery Backup
Battery backup is used to power the site during mains failure and also to protect
the site from short-term interruptions in the mains supply. The backup time is
dependent on for example RBS configuration, traffic load and temperature.