User Manual
Table Of Contents
- toc
- RBS Product Description
- 1 Introduction
- 2 Product Overview
- 3 Dimensions
- 4 Space Requirements
- 5 Environment
- 6 Hardware Units
- 7 Interfaces
- 7.1 External Connections
- 7.2 Test Interface
- 7.3 Operator Interface
- Figure 18 Power System
- 8.1 Power Supply
- 8.2 Battery Backup
- 8.3 Output Power to TM
- 8.4 Power Consumption
- 9 Transmission
- 10 External Alarms
- 11 Standards, Regulations and Dependability
- RBS Product Description
- tables
- Table 1 RBS Weights with Combined Climate Unit
- Table 2 RBS Weights with Heat Exchanger Climate Unit
- Table 3 RBS 2106 Colours
- Table 4 RBS 2106 Climatic Requirements
- Table 5 RBS 2106i and RBS 2106 V3 Climatic Requirements
- Table 6 Sound Pressure Level, Bystander Position without Sound H
- Table 7 Sound Pressure Level, Bystander Position with Sound Hood
- Table 8 Sound Pressure Levels for a Free Standing RBS with Combi
- Table 9 Sound Pressure Levels for an RBS against a Wall, with Co
- Table 10 Sound Pressure Level, Bystander Position without Sound
- Table 11 Sound Pressure Level, Bystander Position with Sound Hoo
- Table 12 Sound Pressure Levels for a Free Standing RBS€2106 with
- Table 13 Sound Pressure Levels for an RBS€2106 Against a Wall, w
- Table 14 Sound Pressure Level, Bystander Position without Sound
- Table 15 Sound Pressure Levels for a Free Standing RBS 2106i or
- Table 16 Sound Pressure Levels for an RBS 2106i or RBS€2106€V3 w
- Table 17 Compliance Boundary Dimensions for the General Public (
- Table 18 Characteristics of Typical Antenna
- Table 19 Maximum Power to Antenna for Various RBS€2106 Configura
- Table 20 Maximum Dimensions
- Table 21 Power Distribution for the TM Space
- Table 22 Connection Field Inlets in RBS 2106i and RBS 2106 V3
- Table 23 OVP Module Capacity
- Table 24 Overvoltage Arrestors
- Table 25 Antenna Connections
- Table 26 External Connections
- Table 27 Optical Indicators
- Table 28 Switches and Circuit Breakers
- Table 29 Power Parameters
- Table 30 Mains Fuses Recommendation
- Table 31 Output Power
- Table 32 Maximum Power Consumption during Battery Charging
Ericsson Internal
DESCRIPTION 13 ( 50 )
/ XSNSIXI 129/1551-LZA 701 0001 Uen
CBC/ XRX/M ( Kai Lian) 2011-05-05 F
Prepared (also subject responsible if other) No.
Approved Checked Date Rev Reference
5 Environment
The RBS 2106 is designed to operate within the limits stated for climatic
requirements listed in the table below, and to withstand ground vibrations as
stated below.
5.1 Operating Environment
Climatic Requirements
The operating environment and climatic specifications are shown in the tables
below.
Table 4 RBS 2106 Climatic Requirements
Description Temperature Relative Humidity
33
C to +45
C
(1)
Normal Conditions
33
C to +40
C
(2)
15 – 100%
Transport
40
C to +70
C
5 – 100%
Storage
25
C to +55
C
10 – 100%
Handling
40
C to +70
C
5 – 100%
(1) Temperature range valid if combined climate unit is used.
(2) Temperature range valid if heat exchanger climate unit is used.
Table 5 RBS 2106i and RBS 2106 V3 Climatic Requirements
Description Temperature Relative Humidity
Normal Conditions
33
C to +45
C
15 – 100%
Transport
40
C to +70
C
5 – 100%
Storage
25
C to +55
C
10 – 100%
Handling
40
C to +70
C
5 – 100%
Ground Vibrations
The RBS 2106 is designed to satisfy earthquake protection according to
IEC 68-2-57.
Levelling
To ensure that the cabinet is level, the floor must be level to within ±3 mm/2000
mm and the floor gradient must be within ±0.1
.
5.2 Environmental Impact
This section describes the effects that the cabinet has on the environment.