Reference Manual Part 1
RBS 2106
Table 16 Output Power
-48 V DC
2 x 200 W
+24 V DC
2 x 250 W
-48 V DC and +24 V DC
200 W + 250 W
Note: Power to the transport module can be distributed to up to 10 internal
users through the optional RU/ADM.
7.4 Power Consumption
The power consumption is shown in the table below.
Table 17 Power Consumption
Climate System Power Consumption, Input Voltage
>200 V AC
Heater Plus Forced-Air Cooling
Only
5570 W
Heater Plus Refrigerated Cooling 5920 W
8 Transmission
The RBS 2106 supports two transmission standards:
• T1 1.5 Mbit/s, 100
, with PLM synchronisation
• E1 2 Mbit/s, 75
, with PCM synchronisation
• E1 2 Mbit/s, 120
, with PCM synchronisation
9 External Alarms
The RBS 2106 supports a maximum of 16 external alarms. The external alarm
device can set the alarm using either an open or a closed condition.
The alarm device connected to the screw terminals must be isolated by relay
contacts. A closed contact (logic zero) is required to be below 2 k
, and an open
contact (logic one) above 100 k
. The current through a closed 0 W contact is
1.2 mA. The voltage between terminals with an open contact is 24 V DC.
The external alarms are defined at the installation. They are defined by using
the OMT, or from the BSC using the remote OMT.
Note: An installed DC/DC Converter is hard-coded to alarm input 16 in the
External Alarm Unit. Pin 16 is therefore unavailable.