Product Description Part 2

RBS 2207
Table 3 Environmenta l specifications
Environmental
Parameters
Normal Operation
(1)
Safe Functio n
Non-
destructive
Conditions
(2)
Temper ature
+5 to +40 C 0 to +45 C -10 to +55 C
Relative Humidity 5 - 85% 5 - 90% 5 - 90%
(1) Normal operation describes the environmental conditions where all units function as specified.
(2) N on-destructive conditions describe environmental stress above the limits for normal
conditions with no function guaranteed and unspecified degradation. When the environmental
stress has dropped to normal conditions, restoring full RBS performance requires no manual
intervention on site. Non-destructive conditions refer to a maximum period of 96 consecutive
hours, and a maximum total of 5.5 days in a three-year period.
Ground Vibrations
The RBS 2207 is tested to withstand random vibrations of up to 0.2 m²/s². It is
also tested for single shocks up to 40 m/s². The cabinet is tested for seismic
exposure with a te st frequ ency of 1 - 35 Hz. Maximum te st level of th e Req uired
Response Spectrum (RRS) is 50 m/s² w ithin 2 - 5 Hz. The shape of RRS is
define d by the ETSI standard.
Levelling
For cabinet levelling purposes, the floor must be level to within ±3 mm/2000
mm and the floor gradient be within ±0.1
.
4.2 Environmen tal Impact
This section describes the effect that th e cabinet has on the e nvironme nt.
Hea t Diss ip ation
The RBS 2207 generates an average heat load of 1000 W. The exact figu re is
dependent upon confguration, equipment and site-specific conditions.
4.3 Compliance Dista nces for Electromagnetic Exposure
The compliance distance is t he minimum separation that should be k ept
between an antenna and a per son in order to ensure that ICNIRP RF exposure
limits are not exceeded.
8 (24)
E
N/LZT 720 0134 Uen R3A