Manual Part 5

Combined Climate Unit
The heater is powered by mains voltage, an d heats the inside air if the startup
tempe rature inside the cabinet is below -5
C. The heater has a capacity of
2 kW.
The CCU measures the retur n air temperature and controls the heater.
4.4 CCU
The Climate Control Unit (C CU) is a processor-based plug-in unit, controllin g
and supervising the climate unit. The CCU provid es the following main
functions:
Monitors internal and external tempera tures
Monitors and controls the internal and external fans
Monitors and controls the heater
Han dles alarms
Supervises mains voltage
Tests the Heat Exchanger Climate Unit
4.5 DC/DC Co nverter
The D C/DC converter operates on +24 V DC supply from the RBS. The
converter feeds -48 V DC supply to the internal air circuit fan, external air circuit
fan in the heat exchanger and the CCU.
4.6 AC/DC Co nverter
The A C/DC converter co nverts AC mains to -48 V DC supply for the internal air
circuit fan, external air circuit fan in the heat exchanger and the CCU, when
the +24 V DC supply is not present.
4.7 Transformer
The transformer supplies the fans, heater, compressor, and AC/DC conve rter
with 230 V AC, independ ently o f the mains input voltage.
The transformer has windings for mains input v oltages of 20 0, 208/220, 230,
240, and 250 V AC.
6 (10)
E
N/LZT 720 0239 Uen R2A