Manual Part 5

ADM-01
Table 3 Input Power
Nominal Voltages Input Power Input Fuse Rating
+24 V DC 2 x 250 W 2 x 15 A
-48 V DC 2 x 200 W 2 x 10 A
+24 and -48 V DC 250 + 200 W 15 and 10 A
Note: The total input power to the ADM-01 must not exceed 500 W.
Output Data
The output data is shown in the table below.
Table 4 Output Connections
Output Connection
Fuse
DC out TM1, pos. 1 5 Screw terminals
0.5 2.5 mm
2
6 A
DC out TM2, pos. 1 5 Screw terminals
0.5 2.5 mm
2
6 A
+24 V DC Out RPV 403 109/604 6 A
4.2 Operator Interface
Output power can be manually switched off using the eleven circuit breakers
on the front panel.
Table 5 Indicators
Indicator
Colour
+24 V DC present Green
-48 V DC present Green