The ten outputs on the ADM-01 are divided into two groups: DC out TM1 and
DC out TM2. The outputs are protected by circuit breakers that function both as
fuses and manual disconnect switches.
The ADM-01 can be fed with +24 V DC or -48 V DC, or both. The feed used is
shown by two indicators on the front panel.
One +24 V DC input is connected to the TM1 output group. The second
+24 V DC input is connected to the TM2 output group.
The two -48 V DC inputs are connected in parallel to both the TM1 and TM2
groups.
The ADM-01 is delivered with a +24 V DC configuration. By removing the front
panel and moving a fuse to the -48 V DC position, an output for distribution of
-48 V DC can be configured. Connection of the voltages is shown on the label
on the front panel.
The output ‘‘Out 100 W’’ is fed +24 V DC from the TM1 input. These outputs
are also protected by circuit breakers that function as fuses and manual
disconnection switches.
4 Interface
The interfaces for the ADM-01 is shown in the figure below.