User Manual
Table Of Contents
- toc
- RBS 2107
- 1 Product Overview
- 2 Dimensions
- 3 Space Requirements
- 4 Environment
- 5 Hardware Units
- 6 Interfaces
- 8 Transmission
- 9 External Alarms
- 10 Standards, Regulations and Dependability
- RBS 2107
- tables
- Table 1 RBS 2107 Weights
- Table 2 RBS 2107 Colours
- Table 3 Climatic Requirements
- Table 4 Compliance Boundary Dimensions for the General Public (G
- Table 5 Characteristics for a Typical Antenna (KRE 101 1916/1)
- Table 6 Maximum Power to Antenna for Various RBS 2107 Configurat
- Table 7 Cable Gland Capacity
- Table 8 Optional Configurations in the DF
- Table 9 OVP Modules Capacity
- Table 10 Antenna Connections
- Table 11 External Connections
- Table 12 Switches and Circuit Breakers
- Table 13 Power Parameters
- Table 14 Mains Fuses Recommendation
- Table 15 Output Power
- Table 16 Power Consumption
RBS 2107
7.4 Power Consumption
The power consumption is shown in the table below.
Table 16 Power Consumption
Power Consumption, Input Voltage
>200 V AC
1700 W
8 Transmission
The RBS 2107 supports two transmission standards:
• T1 1.5 Mbit/s, 100
, with PCM synchronisation
• E1 2 Mbit/s, 75
, with PCM synchronisation
• E1 2 Mbit/s, 120 , with PCM synchronisation
9 External Alarms
The RBS 2107 supports a maximum of 16 external alarms. The external alarm
unit can set the alarm using either an open or a closed condition.
The alarm device connected to the screw terminals must be isolated by relay
contacts. A closed contact (logic zero) is required to be below 2 k
, and an open
contact (logic one) above 100 k
. The current through a closed 0 contact is
1.2 mA. The voltage between terminals with an open contact is 24 V DC.
The external alarms are defined at the installation by using the OMT, or from
the BSC using the remote OMT.
Note: An installed DC/DC converter is hard-coded to alarm input 16 in the
external alarm unit. Pin 16 is therefore unavailable.
Note: An installed smoke detector is hard-coded to alarm input 2 and 3 in the
external alarm unit. Pins 2 and 3 are therefore unavailable.
10 Standards, Regulations and Dependability
This section provides a brief overview of standards, type approval, and EMC.
10.1 Safety Standards
In accordance with market requirements the RBS 2107 complies with the
following product safety standards:
25 (28)
EN/LZT 720 0491 Uen R2A