Reference Manual

Radio Base Station RBS 2206
6 (24) EN/LZT 720 0225 R3A
Layout for RBS Cabinets
P007781A
1000
1000
Unit of measurement: mm
RBS
RBS
RBS
BBS
a=130
o
Figure 2 Floor layout and space requirements
The RBS cabinets and BBS racks are mounted on the floor, and may be
positioned against a wall, back to back, or free standing without contact with
other cabinets.
Expansion cabinets and racks can be positioned to the left or to the right of the
master cabinet. However, expansion to the right is recommended in order to
follow the same standard globally.
A distance of 1000 mm in front of the cabinets and racks for maintenance
work is recommended.
Note: Space for future expansion must be considered as indicated in the
dotted line in the figure above.
Earthquake Requirements
If the RBS cabinet shall fulfill the requirements for earthquake protection, the
space between wall and cabinet is to be at least 100 mm and between
cabinets at least 150 mm.