Hardware Units
The recommended installation is shown in the figure below.
RBS
cabinet
TM
Transmission
equipment
DXU
(DXX)
Lightning
Protection
and
RF filter
P012580A
Figure 12 Recommended TM Installation
The maximum dimensions for the TM are shown in the table below.
Table 20 Maximum Dimensions
Dimension
Size
Panel width
485 mm
Height
445 mm
Depth behind mounting rails
267 mm
Depth behind mounting rails
280 mm
Space in front of mounting rails
(1)
65 mm
(1) For cables and connectors.
Note: The TM space is based on the 19 in. standard housing equipment.
The TM power distribution is shown in the table below.
Table 21 Power Distribution for the TM Space
Type Power
2 × 250 W at +24 V DCDC power distribution
2 × 200 W at
0
48 V DC
Note: The maximum power distribution allowed in the TM space is 300 W.
The available airflow for cooling is 25 g/s (corresponding to approximately
80 85 m
3
/h) at a pressure drop of 60 Pa.
31
129/1551-LZA 701 0001 Uen PF1 | 2010-10-08