Internal Battery Backup
The following battery backup levels can be achieved in the cabinet:
Full: one hour backup time
Half: half an hour backup time
If no TM equipment is used, additional batteries can be installed in the TM
compartment. The backup time will then be enhanced by 100%.
External Battery Backup
Ericsson supplies two external battery backup alternatives: the BBS or the
BBU 9500. Both are connected through the DC filter.
Note: The maximum distance between the RBS and BBS must not exceed
10 meters to prevent damage from, for example, lightning.
8.3 Output Power to TM
The RBS can supply the TM with power according to the table below.
Table 31 Output Power
48 V DC
2 × 200 W
+24 V DC
2 × 250 W
48 V DC and +24 V DC
200 W + 250 W
Note: Power to the transport module can be distributed to up to 10 internal
users through the optional RU/ADM.
8.4 Power Consumption
The power consumption is shown in the table below.
Table 32 Maximum Power Consumption during Battery Charging
RBS Climate System Power Consumption, Input
Voltage >200 V AC
2106 or
2106i
Heat Exchanger Climate Unit 5,570 W
2106 or
2106i
Combined Climate Unit 5,920 W
2106 V3 Heat Exchanger Climate Unit 7,700 W
2106 V3 Combined Climate Unit 8,700 W