User's Manual

RBS 2308 Micro RBS
3 Space Requirements
For installation and maintenance, and proper cooling during operation, the
space in front of the cabinet must be kept clear for a distance of 500 mm,
and there must be at least 250 mm of free space on either side. 300 mm
free space is required above the cabinet. The distance between the cabinet
and the nearest obstruction below (floor, filing cabinet, another RBS, and so
on) must be at least 500 mm.
No free space is needed at the back of the cabinet.
The figure below shows the minimum space requirements and the dimensions
of the RBS in relation to the mounting base (if used). This information can be
used to determine a suitable location with respect to other equipment at the site.
P010156B
Minimum space requirements
Units of measurement: mm
587
139
180
114
145
225
217
433
500
250
300
250
250
250
500
RBS
Figure 2 Space requirements
Mounting Base Holing Pattern
The mounting base of the RBS 2308 has the same holing pattern as that of the
RBS 2302 mounting base, see Figure 2 on page 7.
7 (30)