User's Manual Part 3

RBS 2109 User’s Guide
Table 55 IXU Indicator Status When the RBS is in Operation
IXU temp. Off
Transmission OK On
(2)
(1) Depending on power system configuration.
(2) A, B, C and/or D, depending on transmission configuration.
If the indicators indicate a fault, see the applicable Section below.
9.4.1 Corrective Actions for the IXU
Fault
If the fault indicator is ON (red), IXU HW fault(s) are detected. Perform the
following actions step-by-step until the fault ceases:
Use the OMT to display fault information, see Section 9.3 Fault Localisation
Using OMT on page 158. If the OMT cannot be connected, then proceed
with the steps below
Ensure that the flash card has been properly inserted in the IXU
Replace the IDB and SW on the flash card, see Section 9.5.1 Flash Card
Replacement on page 187
Replace the flash card, see Section 9.5.1 Flash Card Replacement on
page 187
Replace the IXU, see Section 9.5.3 IXU Replacement on page 195
Operational
If the Operational indicator is flashing (green) then configuration activity, initiated
from the BSC, is in progress. Example: SW download or synchronisation is
in progress. A SW download from the BSC can take 30 60 minutes, and
synchronization 5 10 minutes.
Wait until activity is finished, that is until the flashing stops
Local
If the Local indicator is ON (yellow) and it is not possible to bring the IXU into
remote mode, either by using the OMT or by pressing the IXU Local/Remote
button, then perform the following actions step-by-step until the fault ceases:
Reset the IXU
Install a new IDB using a OMT, see chapter Site Installation Tests
Replace the IXU. See Section 9.5.3 IXU Replacement on page 195
1
76
E