User Manual
Table Of Contents
- Contents
- 1 Introduction
- 2 Product Safety Requirements RBS 2000
- 3 Environmental Capabilities
- 3.1 Scope
- 3.2 Terminology
- 3.3 References
- 3.4 Transport -40 C – +70 C
- 3.5 Storage -25 C – +55 C
- 3.6 Handling -40 C – +70 C
- 3.7 Operation Indoor +5 C – +40 C
- 3.8 Operation Outdoor -33 C – +40 C
- 3.9 Operation Outdoor -33 C – +45 C
- 3.10 Operation Outdoor -33 C – +55 C
- 3.11 Operation Mast-Mounted Equipment -33 C – +45 C
- 3.12 Operation Mast-Mounted Equipment -40 C – +55 C
- 4 Climate Protection
- 5 EMC Capabilities
- RBS 2101, Product Description
- RBS 2102, Product Description
- RBS 2103, Product Description
- RBS 2202, Product Description
- RBS 2101, 2102, 2103 & 2202 Radio Configurations
- RBS 2202 Antenna Configurations
- ACCU Description
- BFU Description
- CDU-A Description
- CDU-C Description
- CDU-C+ Description
- CDU-D Description
- DXU Description
- DXU-21 Description
- ECU Description
- PSU -48 V Description
- PSU 230 V Description
- sTRU Single Transceiver Unit Description
- V3 Climate Unit Description
- Glossary
RBS 2101 Macro Outdoor
Table 3 Environmental Specifications
Description
Specification
Operating temperature (with heat
exchanger)
–33 C to +40 C
Operating temperature (with air
conditioner)
–33 C to +45 C
Storage temperature
–25 C to +55 C (Complies with ETS
1.2 in ETS 300 019–1–1 and IEC
721–3–1)
Transport temperature
(non-destructive conditions not
to exceed 96 hours or 5.5 days in a
three-year period)
-40 C to +70 C (Complies with ETS
class 2.3 in Public Transportation in
ETS 300 019–1–2 and IEC 721–3–2)
Relative humidity 15% to 100%
Vibration < 0.2 G
IP Classification
The cabinet complies with IP-55 per IEC 60529.
4.2 Environmental Impact
This section describes the cabinet’s environmental impact.
Table 4 Acoustic Noise and Heat Dissipation
Description
Specification
Acoustic noise 60 dBA (full traffic)40 dBA (50%
load)
(1)
Heat dissipation 1000 W
(1) The acoustic noise dispersion values were measured in a test environment according to the
ISO 9614-2 standard, however deviations from these values may be experienced due to the
nature of materials in the environment where the cabinet is installed. Objects may reflect or
absorb sound and will affect acoustic dispersion.
4.3 Materials
All Ericsson products fulfil the legal, market, and Ericsson requirements.
7 (18)
EN/LZT 720 0219 Uen R2A