User Manual
Table Of Contents
- Contents
- 1 Introduction
- 2 Product Safety Requirements RBS 2000
- 3 Environmental Capabilities
- 3.1 Scope
- 3.2 Terminology
- 3.3 References
- 3.4 Transport -40 C – +70 C
- 3.5 Storage -25 C – +55 C
- 3.6 Handling -40 C – +70 C
- 3.7 Operation Indoor +5 C – +40 C
- 3.8 Operation Outdoor -33 C – +40 C
- 3.9 Operation Outdoor -33 C – +45 C
- 3.10 Operation Outdoor -33 C – +55 C
- 3.11 Operation Mast-Mounted Equipment -33 C – +45 C
- 3.12 Operation Mast-Mounted Equipment -40 C – +55 C
- 4 Climate Protection
- 5 EMC Capabilities
- RBS 2101, Product Description
- RBS 2102, Product Description
- RBS 2103, Product Description
- RBS 2202, Product Description
- RBS 2101, 2102, 2103 & 2202 Radio Configurations
- RBS 2202 Antenna Configurations
- ACCU Description
- BFU Description
- CDU-A Description
- CDU-C Description
- CDU-C+ Description
- CDU-D Description
- DXU Description
- DXU-21 Description
- ECU Description
- PSU -48 V Description
- PSU 230 V Description
- sTRU Single Transceiver Unit Description
- V3 Climate Unit Description
- Glossary
V3 Climate Unit Climate Unit for RBS 2102
1 Product Overview
This section describes the m ain features of the climate unit.
1.1 Main Features
The climate unit maintains climate protection by a combination of air
conditioning, heat exchanging and heating. The units will operate in different
modes depending on the internal temperature of the cabinet. The climate
protection maintains the internal temperature w ithin working range.
The climate unit is dimensioned for any combination of configuration, including
full RF output power with a fully equipped cabinet and 100% traffic load.
2 Dimensions
This section contains the dimensions of the ACCU. Size and w eight are shown
in the table below.
Table 1 Dimensions
Width Height Depth Weight
1100 mm 1000 mm 200 mm 90 kg
3 Power Consumption
This section describes the power consumption of the different units in the
climate unit.
Table 2 Power Consumption
Unit
Max. Power Consumption
Heat exchanger 250 W
Air conditioner (at 230 V AC) 1100 W
Heater (at 230 V AC) 2050 W
Maximum AC (at 230 V AC) 2050 W
Maximum DC 250 W
Maximum AC starting current 25 A
Maximum DC starting current 25 A
3(8)