User Manual

Table Of Contents
V3 Climate Unit Climate Unit for RBS 2102
1 Product Overview
This section describes the m ain features of the climate unit.
1.1 Main Features
The climate unit maintains climate protection by a combination of air
conditioning, heat exchanging and heating. The units will operate in different
modes depending on the internal temperature of the cabinet. The climate
protection maintains the internal temperature w ithin working range.
The climate unit is dimensioned for any combination of configuration, including
full RF output power with a fully equipped cabinet and 100% traffic load.
2 Dimensions
This section contains the dimensions of the ACCU. Size and w eight are shown
in the table below.
Table 1 Dimensions
Width Height Depth Weight
1100 mm 1000 mm 200 mm 90 kg
3 Power Consumption
This section describes the power consumption of the different units in the
climate unit.
Table 2 Power Consumption
Unit
Max. Power Consumption
Heat exchanger 250 W
Air conditioner (at 230 V AC) 1100 W
Heater (at 230 V AC) 2050 W
Maximum AC (at 230 V AC) 2050 W
Maximum DC 250 W
Maximum AC starting current 25 A
Maximum DC starting current 25 A
3(8)
EN/LZT 720 0280 Uen R1A