- 3.4 Transport -40 C – +70 C
- 3.5 Storage -25 C – +55 C
- 3.6 Handling -40 C – +70 C
- 3.7 Operation Indoor +5 C – +40 C
- 3.8 Operation Outdoor -33 C – +40 C
- 3.9 Operation Outdoor -33 C – +45 C
- 3.10 Operation Outdoor -33 C – +55 C
- 3.11 Operation Mast-Mounted Equipment -33 C – +45 C
- 3.12 Operation Mast-Mounted Equipment -40 C – +55 C
- 4 Climate Protection
- 5 EMC Capabilities
- RBS 2101, Product Description
- RBS 2102, Product Description
- RBS 2103, Product Description
- RBS 2202, Product Description
- RBS 2101, 2102, 2103 & 2202 Radio Configurations
- RBS 2202 Antenna Configurations
- ACCU Description
- BFU Description
- CDU-A Description
- CDU-C Description
- CDU-C+ Description
- CDU-D Description
- DXU Description
- DXU-21 Description
- ECU Description
- PSU -48 V Description
- PSU 230 V Description
- sTRU Single Transceiver Unit Description
- V3 Climate Unit Description
- Glossary
BFUBattery Fuse Unit
reaches 60 C, an alarm is sent to the ECU. If it rises
above 65
C, the contactor will trip. The batteries are
reconnected when the temperature falls below 55
C.
Power circuit The high current connection between the rectifiers
and the batteries. The circuit breaker lever indicates
whether it has been tripped or not. The shunt enables
measurement of battery current. The common negative
system voltage is not controlled by the BFU and has
no path through the unit. Thus only positive power is
routed through the BFU.
6 (10)
EN/LZT 720 0233 Uen R1A