User Manual

Table Of Contents
RBS 2103Macro Outdoor
7 Power System
The RBS 2103 power system consists of the 115/230 V AC supply voltage
inputs, internal DC power supply, and the battery back-up system.
7.1 Power Supply
The RBS 2103 operates on 115 V AC or 230 V AC . The mains voltage is
selected by a switch l oacted in the pow er termination box.
Note: A lockable mains disconnect switch must be provided close to the RBS
2103 to facilitate maintenance and repair activities.
7.2 Operating Voltage
The RBS 2103 operating voltage is shown in the table below.
Table 7 Operating Voltage
Voltage Tolerance Frequency
200 240 V AC
(single phase)
± 10% 50 H z
120/240 V AC
(single phase)
±8% 60 Hz
7.3 Power Consumption
The power consumption of the cabinet is shown in the table below.
Table 8 Power C onsumption
Power consumption
Operation
230 V A C 208 V A C
Normal - (operation with
peak load and all time
slots occupied)
1650 W 1650 W
Maximum 3400 W 3400 W
18 (20)
EN/LZT 720 0 221 Ue n R1A