Space Requirements
Space above the RBS Cabinet
P006382A
1770
2070
250
400
600
300
1820
Figure 1 Cabinet Dimensions
The recommended distance between the cabinet and cable ladder is 250 mm.
A shorter distance makes it difficult to exchange fans and may restrict the air
flow. A space of 300 mm is recommended above the cable ladder to make
cable installation work easier.
RBS 2206:
Depth of cabinet including door is 470 mm, of which the door is 70 mm.
RBS 2206 V2:
Depth of cabinet including door is 470 mm, of which the door is 20 mm.