User Manual
Table Of Contents
- toc
- 1 Introduction
- 2 Product Overview
- 3 Dimensions
- Size and Weight
- Surface and Colour
- 4 Space Requirements
- Footprint
- 5 Environment
- 6 Hardware Units
- 7 Interfaces
- 7.1 External Connections
- Connections on DF
- Overvoltage Protection Modules in the RBS 2106i and RBS 2106 V3
- Overvoltage Arrestors for External Alarms in the RBS 2106
- Antenna Connections
- Other External Connections
- External Connections to TM
- Transport Network to TM
- 7.2 Test Interface
- 7.3 Operator Interface
- Indicators
- Buttons
- 8 Power System
- 8.1 Power Supply
- AC Mains Supply Voltage
- External Earth Fault Circuit Breakers
- Mains Fuses
- 8.2 Battery Backup
- Internal Battery Backup
- External Battery Backup
- 8.3 Output Power to TM
- 8.4 Power Consumption
- 9 Transmission
- Optional Transmission Equipment
- 10 External Alarms
- 11 Standards, Regulations and Dependability
PRELIMINARY
Standards, Regulations and Dependability
Dependability
The RBS 2106 is designed for a technical lifetime of 25 years (24-hour
operation). The following preventive maintenance conditions must be fulfilled to
guarantee the availability of the RBS:
Fans The fans must be inspected (and cleaned if
necessary) every year. The lifetime is estimated
to be at least 7 years.
Climate Unit The climate unit must be regularly inspected
and cleaned (the interval is approximately
one year, but depends on the environmental
conditions at the site).
Batteries The batteries must be regularly inspected every
year (for oxide on the pole terminals). The
batteries should be replaced according to the
recommendations of the battery supplier.
Vandal Resistance
The RBS 2106 fulfils Ericsson's requirements for vandal resistance.