User's Manual
Table Of Contents
- toc
- Installation Instruction
- 1 Introduction
- 2 Tools and Documentation
- 3 Installation RRU-N
- Introduction
- Target Group
- 3.1 Prerequisites
- 3.2 Installation Procedure
- Figure 1 Workflow for Installing the RRU-N
- 3.2.1 Unpacking and Checking the Material
- 3.2.2 Installing RRU-N on a Pole or a Mast
- 3.2.3 Installing RRU-N on a Wall
- 3.2.4 Earth Grounding RRU-N
- 3.2.5 Connecting the -48 V DC Power
- 3.2.6 Connecting Optical Fiber Cable and Setting RRU-N Configura
- 3.2.7 Connecting Antenna Cables
- 3.2.8 Installing the Front Sunshield
- 4 Optional Installation External Splitter/Highway Function
- 5 Optional Installation Power Supply Unit-AC Kits
- 6 Optional Installation External Hybrid Combining Unit
- 7 Performing Concluding Routines
- 8 Verifying the Installation
- Installation Instruction
- tables
Ericsson Internal
INSTALLATION INSTR. 31 ( 37 )
/ XKUEMHU 50/1531-LZA 701 0001 Uen
CBC/ XRX ( Jan-Erik Thillberg) 2009-03-09 C
Prepared (also subject responsible if other) No.
Approved Checked Date Rev Reference
This section describes how to install the external PSU-AC on a wall, on a pole,
or a mast and how to connect the cables.
Note: Ericsson provides two types of PSU-AC: PSU-AC-1 and PSU-AC-2.
The PSU-AC-1 installation are shown as the example.
1.
Ensure that the external AC power is switched off before connecting
the cable.
2.
Mount the PSU-AC on a wall, a
pole, or a mast.
Tighten the M10 nuts to a torque
of 25 Nm, using a torque wrench
fitted with a 16 mm socket.
rWWWY``i
or