User guide
)37L( )XX
1 = C14 STRUT
2 = A12 STRUT
)(
STRUT SPAN "L"
"BLANK" = STANDARD FINISH (PG)
XX
BA = BLACK COAT FINISH
CRLP(X
Note 2: Product must be installed with the open side of the channel facing up.
See Figure 1.
NOTE 1
:
PART NUMBERING SCHEME:
CADDY® ROD LOCK Strut
© 2013, 2014 ERICO International Corporation.
3/8", A12 & C14 Strut, 14" - 50" span
www.erico.com
CFS494_D
INSTRUCTION SHEET
1 OF 2
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
TECHNICAL SUPPORT:
WARNING:
ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at 1.
www.erico.com and from your ERICO customer service representative.
ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.2.
All instructions must be completely followed to ensure proper and safe installation and performance. 3.
Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property 4.
damage, serious bodily injury and death.
Products that are manufactured using spring steel components shall be used only in a non-corrosive indoor environment. 5.
All pipe supports, hangers, intermediate components and structural attachments must ONLY be used as described herein and are NEVER to be used for any 6.
other purpose.
NOTE: All load ratings are for static conditions and do not account for dynamic loading such as wind, water or seismic loads, unless otherwise noted.
The customer is responsible for:
a. Conformance to all governing codes.
b. The integrity of structures to which the products are attached, including their capability of safely accepting the loads imposed, as evaluated by a qualified
engineer.
c. Using appropriate industry standard hardware as noted above.
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
1/2 F
1/2 F
L
L1
See Sheet 2 for
Installation.
FIGURE 1
Part Number
SEE NOTE 1
Rod
Size
Strut
Type
Span L Between
Two Rods
in [mm]
Overall Strut
Length L1
in [mm]
F*
lbs [N]
CRLP137L14XX 14 [356] 16 [406] 789 [3,510]
CRLP137L18XX 18 [457] 20 [508] 613 [2,727]
CRLP137L22XX 22 [559] 24 [610] 494 [2,197]
CRLP137L26XX 26 [660] 28 [711] 354 [1,575]
CRLP137L38XX 38 [965] 40 [1,016] 166 [738]
CRLP237L14XX 14 [356] 16 [406] 2,668 [11,868]
CRLP237L18XX 18 [457] 20 [508] 2,075 [9,230]
CRLP237L22XX 22 [559] 24 [610] 1,698 [7,553]
CRLP237L26XX 26 [660] 28 [711] 1,437 [6,392]
CRLP237L38XX 38 [965] 40 [1,016] 983 [4,373]
CRLP237L50XX 50 [1,270] 52 [1,320] 642 [2,856]
*Capacity ratings for strut (F) assumes a uniformly distributed load and includes a hole factor
of 0.92. The load applied to CADDY ROD LOCK Strut should include a factor of safety
appropriate for the application in which the strut is being used. For indoor applications only.
3/8"
C14
A12