User guide
EG_GenPro2xe_1003_UG_005_UK Page 55 / 63
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
Dct_427_00
8.2.3.2 Output – GenPro 23e
Table: Characteristics of the open-collector output
Characteristics Symbols Conditions Max. Unit
max. tension V
CE0
Open transmitter 80 V
DC
max. tension V
CES
V
BE
= 0 V 60 V
DC
Collector current I
C
1 A
Saturation tension V
CEsat
I
C
= 500 mA 1.3 V
Dissipation P
Ttot
T
amb
25 °C, T
j
= 110 °C 0.78 W
Electric scheme of the output
No protection is provided. The user must respect the values of the table above.
8.2.3.3 Analog input – GenPro 23e
As an option on the GenPro 23e, it is possible to have an analog input instead of the opto-coupled input E2.
This analog input allows to do a measure in tension (contact us).
Table: Characteristics of the analog input option
Characteristics Min. value Max. value
Command tension 0 V DC 10 V DC
Internal electrical scheme of the analog input option