Technical data

25
· timer Ò1 – time for initial pellets feeding (01:30 min.)
· timer Ò2 – maximum ignition time (07.00 min.)
· timer Ò3 – filter S (10.00 sec.)
· timer Ò4 – time for pellets feeding in standing mode (12:00 sec.)
· timer Ò5 – time for burning after stop-command (10:00 min.)
· timer Ò6 – time for burning in standing mode (12:00 sec.)
· timer Ò7 – time for burning of a first dosage (00:30 min.)
· timer Ò8 – filter (05.00 sec.)
· counter Ñ1 – counter of the ignition attempts (0003)
The available for settings parameters during work are the following:
timer Ò1 – time for initial pellets feeding
timer Ò2 – maximum ignition time
timer Ò4 – time for pellets feeding in standing mode
timer Ò5 – time for burning after stop-command
timer Ò6 – time for burning in standing mode
timer Ò7 – time for burning of a first dosage
counter Ñ1 – counter of the ignition attempts Remark: As soon as flame
from the photosensor is registered, the attempts for new ignition end. The number
of the ignition attempts is n-1, where n is the setting of counter C1. If at n-1
attempts the ignition is not reached, at the n attempt (in this case the third
attempt) the system gets into emergency mode (a signal lamp ALARM lights).
An intervention is necessary (check the reason for the unsuccessful attempts).
The alarm clears through the burner turning off by its switch.
With their help and with adjusting the air valve can be set the burner power (an
analyze of the flue gases is necessary to be made with appropriate gauge
instruments, so the burning process will be optimized)