4. If the Add Signal and Discharge Signal are always valid, the indicator will automatically 
execute the procedure repeatedly. 
  Table 6-2 describes the working process of 
quantitative scale subtraction by program 
step.
Display method of program step
 Set Parameter 7B ofSET  0to 4; under running status, 
the  auxiliary  display  of  the  indicator  will  show  the  current  program  step  number  in  forms  of 
‘Step**’. 
Table 6-1 Description of Program Step of Additive Quantitative Scale 
Program 
step 
Description 
1  Wait for stable display light to be ON and Add Signal to be valid; 
tare  is  automatically  performed,  the  timer  will  be  T0  and  go  to 
program step 2 
2 
Start quick feed of material 1. If T1 is 0start the slow feed of 
material  1  at  same  time.  When  T0  is  over,  weight  inspection  is 
started.
If the loaded value reaches to batching value of material 1 
minus quick feed lead of material 1, turn off quick feed of material 
1.The timer will be T1 and go to program step 3. 
3  Timing is over, go to program step 4 and the timer is T0 
4  Start slow feed of material 1, timing is over and weight inspection 
is started. If the loaded value reaches to batching value of material 
1 minus slow feed lead of material 1, turn off slow feed of material 
1.Timer will be T2 and go to program step 5 
5  The timing is  over.  If the lead correction is  allowed, modify  the 
slow feed lead of material 1, and go to program step 6. 
6  If the  material 1  weight is  qualified, the qualified signal will be 
output and it will go to program step 9, the timer will be T5. If it is 
out  of  the  tolerance,  output  the  out-of-tolerance  signal. If  the 
weight is less than the batching value of material 1 minus tolerance 