2-10
2-5 DIP Switches
DIP switches (1 to 4) are equipped on side of the display unit.
When setting the DIP switches, turn the power off.
(Use USB-CFREC)
DIPSW1, 2, 3 (Terminating Resistance Setting)
• MJ1 can be used for RS-232C or RS-485 (2-wire) connection. For the following connections, set DIPSW1 to
the ON position.
- Master station for multi-link2 connection
- Connection with a controller (PLC, temperature controller, etc.) via RS-485
- Connection with the card recorder “CREC” (optional)
- Connection with the serial extension I/O “V-I/O” (optional)
- Connection to the @E. Terminal unit at the termination of V-link connection via RS-485
• MJ2 can be used for RS-232C, RS-422 (4-wire) or RS-485 (2-wire) connection.
For connection via RS-485 (2-wire connection), set the DIPSW3 to the ON position. For connection via RS-422
(4-wire connection), set the DIPSW2,3 to the ON positions.
DIP switch #4* (Auto-uploading from CF)
Set the DIPSW4 to the ON position when auto-loading a screen data file saved on a CF card.
Procedure
1. Have a CF card to which the screen data is loaded using the V-SFT-5 editor (for the loading procedure, refer to the
V8 Series Reference Manual(1055NEx)).
2. Power off the display unit and set the DIPSW4 to the ON position. Insert a CF card to USB CF card recorder
(USB-CFREC) connected with USB-A port.
3. Turn the V806 unit on. The screen data is automatically loaded into the FLASH memory of the display unit.
* Be sure to set the DIPSW4 to the OFF position if the auto-uploading function is not being used.