5 Protection, Troubleshooting and Maintenance
5.1 Protection
PV Array Short Circuit
If PV array short circuit occurs, clear it to resume normal charge automatically.
Load Overload
If the load current exceeds the rated current of controller≥1.05 times rated discharge
current, the controller will disconnect the load. Overloading must be cleared up, then
pressing the switch button.
Load Short Circuit
Fully protected against load wiring short-circuit≥2 times rated discharge current. After
one automatic load reconnect attempt, the fault must be cleared by restarting the
controller or pressing the switch button.
PV Reverse Polarity
Fully protection against PV reverse polarity, no damage to the controller will result.
Correct the miswire to resume normal operation.
Battery Reverse Polarity
Fully protection against battery reverse polarity, no damage to the controller will result.
Correct the miswire to resume normal operation.
Battery working voltage error
If battery voltage does not match controller working voltage, controller will stop working.
After correcting the voltage, the failure can be eliminated through pushing load button.
Damaged Temperature Sensor
If the temperature sensor short-circuited or damaged, the controller will be charging or
discharging at the default temperature 25 to prevent the battery damaged from
overcharging or over discharged.
Overheating Protection
If the temperature of the controller heat sink exceeds 85, the controller will
automatically start the overheating protection and stop the charging and discharging.
When the temperature is below 75, the controller will resume to work.