User Manual
7
3 Installation Instructions
3.1 Mounting
Read through the entire installation section first before beginning installation.
Be very careful when working with batteries. Wear eye protection. Have fresh water
available to wash and clean any contact with battery acid.
Uses insulated tools and avoid placing metal objects near the batteries.
Explosive battery gasses may be present during charging. So well ventilation of battery
box is recommended.
Avoid direct sunlight and do not install in locations where water can enter the controller.
Loose power connections and/or corroded wires may result in resistive connections that
melt wire insulation, burn surrounding materials, or even cause fire. Ensure tight
connections and use cable clamps to secure cables and prevent them from swaying in
mobile applications.
Gel, Sealed or Flooded batteries are recommended, other kinds please refer to the battery
manufacturer.
Battery connection may be wired to one battery or a bank of batteries. The following
instructions refer to a singular battery, but it is implied that the battery connection can be
made to either one battery or a group of batteries in a battery bank.
Select the system cables according to 3A/mm2 current density.
CAUTION: The ViewStar controller requires at least 150mm of
clearance above and below for proper air flow. Ventilation is
highly recommended if mounted in an enclosure.
WARNING: Risk of explosion! Never install the controller in a
sealed enclose with flooded batteries! Do not install in a confined
area where battery gassed can accumulate.