User Manual

24
Parameter
Detail
ON
The load will turn on automatically after the controller is
initialized. If the battery power is enough and the controller
works well, load will keep on.
OFF
The load will turn off after the controller is initialized. Only
when the load turn on manually, load can be output. If the
battery power is enough and the controller works well, load
will keep on.
Light On/Off
Manual
Light On+Timer
Time
Light On/Off
Light On/Off
On 05.0V T 10 M
Off 06.0V T 10 M
Load control mode can be set to light control in this interface. Parameters in
the table below:
Parameter
Detail
Night Time
Threshold
Voltage
When solar module voltage goes below the point of
NTTV (Night Time Threshold Voltage), the solar
controller will recognize the starting voltage and turn on
the load after pre-set time delay when the battery power
is enough and the controller works well
Day Time
Threshold
Voltage
When solar module voltage goes above the point of
DTTV (Day Time Threshold Voltage), the solar
controller will recognize the starting voltage and turn off
the load after pre-set time delay
Delay time
Solar energy confirms delay time. If the solar energy
meets the condition to the action, it will be execute. The
range of delay time value is 0 to 99 minutes
Light On + Timer
Manual
Light On/Off
Time
Light On+Timer
Light On +Timer
On 05.0V T 10 m
Off 06.0V T 10 m
Night Time 12:00
Light On +Timer
On T1 01H:00M
On T2 01H:00M
Load control mode can be set to light + timer control in this interface.
Parameters in the table below: