Datasheet
4-line filters  B84131 
for installations and systems 
Technical data and measuring conditions 
Rated voltage V
R 
440/250 V AC, 50/60 Hz 
Rated current I
R 
Referred to 40 °C ambient temperature 
Test voltage V
test 
1770 V DC, 2 s (line/line) 
2700 V DC, 2 s (lines/case) 
Leakage current l
leak 
At 400 V AC, 50 Hz 
Climatic category (IEC 60068-1)  25/085/21 (–25 °C/+85 °C/21 days damp heat test) 
Approvals  EN 133200, UL 1283, CSA C22.2 No.8 
Characteristics and ordering codes 
V
R 
AC 
V 
I
R 
A 
I
leak 
mA 
Approx. 
weight 
kg 
Ordering code  Approvals 
440/250  6  < 3.5  0.8  B84131A0006A001  ×  – 
16  < 3.5  1.5  B84131M0003A116  × 
25  < 3.5  2.3  B84131M0001G125  × 
35  < 3.5  2.3  B84131M0001G135  × 
35  < 3.5  2.3  B84131M0001H135  –  × 
50  < 3.5  4.5  B84131M0002G150  × 
63  < 3.5  4.5  B84131M0002G163  × 
80  < 3.5  12.5  B84131M0004G180  ×  – 
125  < 3.5  12.5  B84131M0004G225  ×  – 
– 
× × 
× 
× × 
× 
× × 
× × 
– 
– 
× = approval granted 
Please read Cautions and warnings and 
Important notes at the end of this document. 
01/06 3 