Datasheet

2-line filters B84115E
SIFI-E for high insertion loss
Circuit diagram
L
LINE LOAD
L’
N N’
SSB0270-8
Technical data and measuring conditions
Rated voltage V
R
250 V DC/AC, 50/60 Hz
Rated current I
R
Referred to 40 °C ambient temperature
Test voltage V
test
1414 V DC, 2 s (line/line)
2700 V DC, 2 s (lines/case)
Leakage current l
leak
At 230 V AC, 50 Hz
Climatic category (IEC 60068-1) 25/085/21 (–25 °C/+85 °C/21 days damp heat test)
Approvals EN 133200, UL 1283, CSA C22.2 No.8
Characteristics and ordering codes
I
R
A
C
R
L
R
mH
I
leak
mA
Case
style
Appr.
weight
g
Ordering code Mounting plate
for top-hat rail
(ordering code)
V
R
= 250 V DC/AC, 50/60 Hz
3 0.47 µF (X2)
+
2 × 4.7 nF (Y2)
2 × 0.27
+
2 × 16
< 0.5 A
B
K
210
210
270
B84115E0000A030
B84115E0000B030
B84115E0000K030
C62122A0132B092
6 0.47 µF (X2)
+
2 × 22 nF (Y2)
2 × 0.10
+
2 × 4.7
< 3.5 A
B
K
510
510
510
B84115E0000A060
B84115E0000B060
B84115E0000K060
C62122A0132B095
10 0.47 µF (X2)
+
2 × 22 nF (Y2)
2 × 0.047
+
2 × 3.6
< 3.5 A
B
690
690
B84115E0000A110
B84115E0000B110
C62122A0132B095
Please read Cautions and warnings and
Important notes at the end of this document.
01/06 3