Datasheet
4-line filters B84108
for installations and systems
Technical data and measuring conditions
Rated voltage V
R
440/250 V AC, 50/60 Hz
Rated current I
R
Referred to 40 °C ambient temperature
Test voltage V
test
1414 V DC, 2 s (line/line)
2700 V DC, 2 s (lines/case)
Leakage current l
leak
At 400 V AC, 50 Hz
Climatic category (IEC 60068-1) 25/085/21 (–25 °C/+85 °C/21 days damp heat test)
Approvals EN 133200
Characteristics and ordering codes
V
R
AC
V
I
R
A
I
leak
mA
Approx.
weight
g
Ordering code Approvals
440/250
10
< 3.5 220 B84108S1004A110
×
20
< 3.5 220 B84108S1004A120
×
× = approval granted
Dimensional drawing
84.5
15 14
31.5
74.5
63.5
89.5
50.8
4.7
Tab connector A6.3 x 0.8
38+0.8
SSB0335-R-E
Please read Cautions and warnings and
Important notes at the end of this document.
01/06 3