Technical data

26
Envoy Installation, Commissioning & Operating Manual
Set Up Network
Once all cards are fitted , set Dil switch addresses on PCENV-NET. Designate one panel as the
‘master’
Dil switch positions:-
Both off = Master
1 off 2 on = First repeater / panel
1 on 2 off = Second repeater / panel
1 on 2 on = Third repeater / panel
Each panel must have a different setting.
For monitoring purposes, the master must be instructed how many panels are in the network. If it
changes, the panel will show system fault and will warble.
To enter quantity of panels:
At the master panel (panel with both address switches ‘off’)
1. Turn off power to panel
2. Press and hold button 4 on keypad whilst powering panel back up. (when powered up the panel
will beep continuously)
3. Enter total number of panels in the network, including the master, by pressing the relevant
keypad number (1-4), followed by the enter button.
When all panels are addressed correctly, the master is set-up and all panels are powered, the TX and
RX LEDs will flicker on all panels to confirm communication between panels. In the event of a ‘comms’
failure the affected panels will warble and show a fault. Note:- panels will function as stand alone in the
event of ‘comms’ failure.
Network Control and Operation
As standard, the network / repeater panels are configured to provide basic operation. If non standard
functioning is required, please contact our technical department for advice.
The table below details the functionality of the system.
Local = Operates and displays at the local panel level only
Global = Operates and displays on all panels simultaneously
Controls
Key switch = Local ‘panel controls’ only
Evacuate = Global
Silence = Global, silence alarms and fault tone
Reset = Global
Test Mode = Local zones only
Disable = Local zones only
Test LEDs = Local
Enter = Local fault mute (without key-switch)