Technical data

18
Envoy Installation, Commissioning & Operating Manual
Initialisation of Zone Cards
For added security, the master card (PCENV-M-5) keeps a log of fitted zone cards and will indicate a
system fault, with a warbling tone, if zone cards are removed, or cease to function. To achieve this,
zone cards are logged ‘on’ and ‘off’ of the panel.
Proceed as follow:
1 Ensure panel is completely powered down by disconnecting both mains and battery supplies.
2 Insert, or remove, required zone card(s), ensuring pins are securely located.
3 Press and hold button No.1 on keypad and at the same time apply either battery or mains power.
4 Observe the zone fault illuminating on each zone card, this indicates acknowledgment of
‘learning’ mode.
5 Release button 1 and press Reset to clear fault indications and ‘ARW’.
If a panel should start to warble and show system fault, check the following:-
If a PCENV-NET card is fitted, refer to network instructions.
If no network is present, check whether zone cards will function i.e. go into fire, or fault.
If a zone card appears to be faulty, replace it, or remove it.
If a problem persists, try to re-log the card by following the procedure 1-5 again, as above.
If ‘Disablement’ indicator is on, but no zone is illuminated, it is possible that the internal memory is
out of synchronisation. This can be corrected by the following procedure:
1 Completely power down panel
2 Press and hold button No.2 on keypad whilst powering up
3 The panel will enter a self diagnosis mode, which resets the memory
4 Pressing the ’Enter’ button will step through a test routine, which will operate LEDs and outputs in
a sequence.
To exit this mode, power down the panel and power up again, as normal.