Specifications

93
TM
Diagrams are for reference only.
Consult the appropriate installation sheet for wiring details.
REFERENCE SECTION
SAC BUS WIRE LENGTH TABLESSAC BUS WIRE LENGTH TABLES
SAC BUS WIRE LENGTH TABLESSAC BUS WIRE LENGTH TABLES
SAC BUS WIRE LENGTH TABLES
Table D-2: SAC bus wire lengths versus number of doors and current loads using
14 AWG wire
Doors Load (mA)
70
100 150 200 250 300 350 400 450 500 550 600 650
1 4000 4000 4000 3000 2400 2000 1750 1500 1360 1200 1100 1000 940
2 4000 4000 2700 2000 1600 1360 1160 1000 900 800 740 680 620
3 4000 3000 2040 1500 1200 1020 870 750 660 600 555 510 471
4 3480 2400 1600 1200 960 800 700 600 544 480 436 400 376
5 2900 2000 1365 1000 800 675 575 500 455 405 365 335 315
6 2460 1710 1140 870 690 582 492 438 390 348 312 X X
7 2170 1505 1015 756 602 511 434 378 336 301 X X X
8 1920 1360 904 680 544 448 384 336 X X X X X
9 1710 1215 810 612 477 405 351 X X X X X X
10 1550 1100 740 550 440 370 310 X X X X X X
11 1430 1012 682 506 407 341 X X X X X X X
12 1344 936 624 468 372 X X X X X X X X
13 1248 858 585 429 351 X X X X X X X X
14 1162 812 532 406 322 X X X X X X X X
15 1095 750 510 375 X X X X X X X X X
16 1024 720 480 352 X X X X X X X X X
17 969 680 442 340 X X X X X X X X X
18 918 630 414 X X X X X X X X X X
19 874 608 399 X X X X X X X X X X
20 820 580 380 X X X X X X X X X X
Note: All distance measurements given in feet. X means that the 3-PPS/M will not
support these devices at any distance.