Specifications

91
TM
Diagrams are for reference only.
Consult the appropriate installation sheet for wiring details.
SAC BUS POWERSAC BUS POWER
SAC BUS POWERSAC BUS POWER
SAC BUS POWER
REFERENCE SECTION
Providing adequate voltage for devices
To determine whether each CRC and KPDISP will have adequate input voltage,
calculate the voltage drops along the SAC bus. Voltage drops can be estimated or
actual.
Estimated voltage drop
To estimate the voltage drop use Table D-1 and Table D-2, which show the maximum
wire length for a given number of doors at a given current load. The tables assume
even spacing between the doors and an equal load at each door.
1. First, determine the load per door by adding the alarm currents of the CRC, door
lock, card reader, and sounder.
2. Determine the number of doors you need to secure. Find the number of doors
Table D-1 then search across that row for the column with the current you
calculated in step 1.
3. The intersection gives the maximum distance from the 3-PPS/M or remote power
supply to the last door.
4. If the distance to the last door in your installation is less than this distance no
further calculations are needed.
5. If the distance to the last door in you installation is greater than this distance
check TYable D-2 using steps 1 through 4.
6. If changing the gauge of the wire does not work, you must run a second power
line, or divide the SAC bus and add a remote power supply. In either case, recheck
your estimates.
For example: You are putting a CRC, a strike rated at 250 mA @ 12 Vdc, a CR-5395
and a CRCSND at 8 doors. The furthest door is 500 feet from the control.
Using step 1 above, you determine that the total alarm current for this door is 149
mA. In Table D-1 (for 16 AWG), find 8 in the Doors column, go across this row to the
150 mA column. The intersection shows a maximum length of 584 feet. Since the
distance from the control panel to the last door is less than 584 feet, no further
calculations are needed.
Actual voltage drop
To calculate the actual voltage drop based on the actual load for each device and the
actual distance between each device, follow the steps on the next page.