Specifications
89
TM
Diagrams are for reference only.
Consult the appropriate installation sheet for wiring details.
3-SAC DATA BUS & 3-SAC POWER3-SAC DATA BUS & 3-SAC POWER
3-SAC DATA BUS & 3-SAC POWER3-SAC DATA BUS & 3-SAC POWER
3-SAC DATA BUS & 3-SAC POWER
REFERENCE SECTION
3-SAC Data Bus
SAC bus wiring riquirements
Type: unshielded, twisted pair, > 6 twists per foot
Maximum bus length: 4,000 ft (1,220 m) @ 25 pF/ft
Maximum total circuit capacitance: 0.1 µF
Maximum total circuit resistance: 52 Ohms
3-SAC Power
This topic provides information to help you determine whether:
• A power supply must be added to the SAC bus
• Adequate voltage will be available to CRCs and KPDISPs on the SAC bus
• The standby battery in each CRC is properly sized
Determining the need for a remote power supply
The need for additional power is dictated by the current drawn by the devices on the
SAC bus. Each 3-PPS/M can supply a total of 7 A through two 3.5 A outputs. Each
SAC line can therefore draw a maximum of 3.5 A. This consists of the current drawn by
the CRCs and KPDISPs plus any readers, strikes, or maglocks.
If the load on the 3-PPS/M supply is greater than 3.5 A, you’ll need to split the devices
over two SAC buses, or add a remote power supply.
To determine the total load on the 3-PPS/M:
1. Complete Form A (below) to calculate the system alarm and standby load current.
2. Total the columns to determine the Total Alarm Load and Total Amp Hours. These
two totals will be used in later calculations.
3. If the Total Alarm Load is greater than 3.5 A, the devices must be divided between
two SAC buses, each with a separate supply — OR — a remote power supply
must be installed.
4. If a remote power supply is used a ground wire must be between the 3-SAC and
the remote power supply.