SIGNATURE DATA CIRCUIT MAXIMUM WIRE LENGTH CALCULATIONSSIGNATURE DATA CIRCUIT MAXIMUM WIRE LENGTH CALCULATIONS
SIGNATURE DATA CIRCUIT MAXIMUM WIRE LENGTH CALCULATIONSSIGNATURE DATA CIRCUIT MAXIMUM WIRE LENGTH CALCULATIONS
SIGNATURE DATA CIRCUIT MAXIMUM WIRE LENGTH CALCULATIONS
REFERENCE SECTION
Use this worksheet to determine the maximum amount of wire you can use to
construct a Signature loop.
Step 1: Step 1:
Step 1: Step 1:
Step 1: Calculate the total amount of wire you can used based on the cable
manufacturer’s capacitance per foot rating. Total amount of wire shall not exceed the
values listed in Table .
Determining the total loop length
The total loop length is the sum of the lengths of all the wire segments installed in the
data circuit.
If the cable manufacturer’s data indicates the capacitance per foot of the cable, the
following method may be used to determine the maximum total loop length.
Note: In no case may the total loop length of a Signature data circuit exceed 20,000
feet (6,098 meters).
Wire Size
Wire type 14 AWG 16 AWG 18 AWG
Twisted pair 13,157 ft (4,010 m) 13,888 ft (4,233 m) 20,000 ft (6,096 m)
Twisted-shielded pair 5,952 ft (1,814 m) 6,098 ft (1,859 m) 8,621 ft (2,628 m)
Non-twisted,
non-shielded pair
20,000 ft (6,096 m) 20,000 ft (6,096 m) 20,000 ft (6,096 m)
The total length of all the cable installed in the Signature data circuit can not exceed
the values listed below:
Table C-1: Maximum amount of wire you can use to construct a Signature loop
Signature
Controller Module
10
6
12
5
1