Specifications
77
TM
Diagrams are for reference only.
Consult the appropriate installation sheet for wiring details.
Notification appliance circuit maximum wire length calculation
Use this worksheet to determine the maximum wire length of a notification appliance
circuit. Fill in one worksheet for each NAC connected to the panel.
Maximum signal loss allowed [1] V
x 1000
Wire resistance per 1000 ft/pair [2] ÷ ohms
Total operating current required [3] ÷ A
Maximum circuit length ft
FireShield maximum wire length calculation notesFireShield maximum wire length calculation notes
FireShield maximum wire length calculation notesFireShield maximum wire length calculation notes
FireShield maximum wire length calculation notes
[1] 1.6 V for 230 V at 50 Hz, 1.8 V for 230 V at 60 Hz, 1.9 V for 120 V at 60 Hz
[2] Use wire resistance from Table 1.
[3] Use the
20 Vdc VFWR Average/Mean Operating Current
ratings found on the
installation or catalog sheet of each device.
QuickStart maximum wire length calculation notesQuickStart maximum wire length calculation notes
QuickStart maximum wire length calculation notesQuickStart maximum wire length calculation notes
QuickStart maximum wire length calculation notes
[1] For worst case estimates, assume a 1.5 V line loss and all appliances are clustered
at the end of the circuit.
[2] Use wire resistance from Table 1.
[3] Use the
20 Vdc VFWR Average/Mean Operating Current
ratings found on the
installation or catalog sheet of each device.
EST3 maximum wire length calculation notesEST3 maximum wire length calculation notes
EST3 maximum wire length calculation notesEST3 maximum wire length calculation notes
EST3 maximum wire length calculation notes
[1] For worst case estimates, assume a 3.4 V line loss and all appliances are clustered
at the end of the circuit.
[2] Use wire resistance from Table 1.
[3] Use the
20 Vdc Average/Mean Operating Current
ratings found on the
installation or catalog sheet of each device.
24 VDC NAC WIRE LENGTH24 VDC NAC WIRE LENGTH
24 VDC NAC WIRE LENGTH24 VDC NAC WIRE LENGTH
24 VDC NAC WIRE LENGTH
REFERENCE SECTION