Specifications
75
TM
Diagrams are for reference only.
Consult the appropriate installation sheet for wiring details.
24 VDC NAC WIRE LENGTH24 VDC NAC WIRE LENGTH
24 VDC NAC WIRE LENGTH24 VDC NAC WIRE LENGTH
24 VDC NAC WIRE LENGTH
REFERENCE SECTION
General Information
The 24 Vdc notification appliance circuits must be a minimum of 18 AWG (0.75 mm
2
)
pair. Terminals on FireShield, QuickStart and EST3 will support 18-12 AWG wire.
Circuit length limits are determined using the maximum allowable circuit resistance and
cable manufacturer’s specifications.
Circuit capacity
FireShield notification appliance circuits are rated at 1.5 amps each at 24 Vdc FWR.
QuickStart notification appliance circuits are rated at 1 or 2 amps each at 24 Vdc FWR.
EST3 notification appliance circuits are rated at 3.5 amps each at 24 Vdc regulated.
Table A-1: Wire resistance ratings to use for wire length calculations
Wire Size Resistance per 1000 ft pair (ohms)
18 AWG / (0.75 mm
2
) 13.0
16 AWG / (1.0 mm
2
) 8.0
14 AWG / (1.50 mm
2
) 5.2
12 AWG / (2.5 mm
2
) 3.5