SIGA-IM Fault Isolator Module
The SIGA-IM Isolator Module enables part of the Signature data loop to continue
operating should a short circuit occur. The module can be wired into a Class A data
loop at any point.
MODULE (TWO-GANG STANDARD MOUNT)MODULE (TWO-GANG STANDARD MOUNT)
MODULE (TWO-GANG STANDARD MOUNT)MODULE (TWO-GANG STANDARD MOUNT)
MODULE (TWO-GANG STANDARD MOUNT)
SIGNATURE MODULES
Green LED
(normal - flashing)
TB1
DATA OUT (+)
DATA OUT (-)
DATA IN (+)
DATA IN (-)
From Signature Loop
Controller or Previous
Device
To Next Device or EOL
Resistor supplied with
UL/ULC Listed Control Panel
4
3
5
1
6
4
3
2
5
For maximum wire resistance,
refer to the appropriate
manufacturer’s documentation.
Max. #12 AWG (2.5mm²)wire.
Refer to Signature Loop
Controller Installation Sheet
for wiring specifications.
This module should be used
only with Class A wiring.
Maximum circuit resistance
between isolators is 6 ohms.
All wiring is power-limited
and supervised.
This part is removed
from circuit
SIGA-IMSIGA-IM
SHORT
CIRCUIT
Typical Class A Configuration
Data Return
Signature Loop Controller
Data Out
This part is removed
from the circuit
SIGA-IM
SIGA-IM
SHORT
CIRCUIT
Data Return
Data Out
Signature Loop Controller
Typical Class A Configuration
with Class B T-Taps