Specifications

60
Diagrams are for reference only.
Consult the appropriate installation sheet for wiring details.
TM
OUTPUT MODULES (GANG MOUNT)OUTPUT MODULES (GANG MOUNT)
OUTPUT MODULES (GANG MOUNT)OUTPUT MODULES (GANG MOUNT)
OUTPUT MODULES (GANG MOUNT)
SIGNATURE MODULES
SIGA-CC2 Wiring
The SIGA-UM Universal Class A/B Module is installed to a
standard North American 2-gang electrical box. Separate I/O
and data loop connections are made to each module. The
SIGA-UM may be used to connect any one of the following:
two Class B or one Class A Initiating Device Circuits; one
Class A or B Notification Appliance Circuit; one Class A or
B Circuit for 2-wire Smoke Detectors; one Form “C”
(NO/NC) Dry Output Contact Relay.
SIGA-CC1 Single Input Signal Modules and SIGA-CC2
Dual Input Signal Modules are used for connecting,
upon command from the loop controller, supervised Class B signal or telephone circuits
to their respective power inputs. The power inputs may be polarized 24 Vdc to operate
audible and visible signal appliances or 25 and 70 VRMS to operate audio evacuation
speakers and firefighter’s telephones. The actual operation of the SIGA-CC1 and
SIGA-CC2 is determined by the “personality code” selected by the installer.
UL/ULC Listed
47K EOLW
UL/ULC Listed
47K EOLW
Typical Notification Appliance Circuit
Typical Speaker Circuit
Personality
Code 7
Personality
Code 7
Bi-polar Transient Protector
(P/N 235196P)
+
+
__
+
+
__
+
+
__
B
C
D
C
D
C