Specifications

50
Diagrams are for reference only.
Consult the appropriate installation sheet for wiring details.
TM
INTEGRITYINTEGRITY
INTEGRITYINTEGRITY
INTEGRITY
NOTIFICATION APPLIANCES
964 and 965 Series Speaker and Speaker/Strobe
To Listed Fire
Alarm Control
Panel
(signal circuit)
End-of-line
resistor
(supplied with
control panel)
R/W
+
-
B/W
R/W
+
-
B/W
R/W
R/W
B/WB/W
-
+
KEY:
A signal matching the input voltage rating of the speaker (25 or 70 Vrms)
CAUTION: Electrical supervision requires wire run to be broken at each device.
Place an
end-of-line
resistor
on the
last device.
(Resistor
supplied with
control panel.)
- Speaker
Symbol
S
ST
U
W
S
T
UW
S
KEY:
To Listed
Control
Panel
Audio
Output
S
These Speakers and Speaker/Strobes are available in either 4 inch or 8 inch size.
964 Series speakers connect to 25 Vrms audio circuits.
965 Series speakers connect to 70 Vrms audio circuits. The strobe must be connected to
signal circuits which output a constant (not pulsed) 24 Vdc voltage.
Models (S=square):
964-1A-4S same as those listed on page 49
B
C
B
C