Specifications

47
TM
Diagrams are for reference only.
Consult the appropriate installation sheet for wiring details.
GENESISGENESIS
GENESISGENESIS
GENESIS
NOTIFICATION APPLIANCES
Genesis (wall mount) Speakers
All Genesis speakers include a DC blocking capacitor to
allow electrical supervision of the audio distribution
circuit. Models for 25 V
RMS
and 70 V
RMS
circuits are
available. ¼ W to 2 W operation is selectable with a
conveniently-located switch on the bottom of the device.
Models:
G4-S2VM 25 Volt Speaker-strobe with selectable
15, 30, 75, or 110 cd output
G4-S7VM 70 Volt Speaker with selectable
15, 30, 75, or 110 cd output
G4-S2 25 Volt Speaker
G4-S7 70 Volt Speaker
G1M-RM Synchronization Output Module (1-gang)
S
SPKR
S+
C
S-
Speaker-only Wiriing
Polarity shown in
alarm condition
To next device
or end of line
device
++
S
SPKR
S+
C
S-
To listed fire alarm control panel
(supervised amplifier signal circuit
– 25.2 or 70.7V rms)
SPKR
S+
C
S-
Speaker-Strobe Wiring
Polarity shown in
alarm condition
To next device
or end of line
device
++
SPKR
S+
C
S-
S S
++
To listed fire alarm control panel
(supervised signal circuit
– 20-24 Vdc)
To listed fire alarm control panel
(supervised amplifier signal circuit
– 25.2 or 70.7V rms)
C
C
C
C
B
B