Specifications
22
Diagrams are for reference only.
Consult the appropriate installation sheet for wiring details.
TM
CONTROL PANELS
CIRCUIT REFERENCE TABLE - EST3CIRCUIT REFERENCE TABLE - EST3
CIRCUIT REFERENCE TABLE - EST3CIRCUIT REFERENCE TABLE - EST3
CIRCUIT REFERENCE TABLE - EST3
For cable part numbers turn to the Paige/EST Cross Reference Tables on the pages
indicated below.
Ref/Pg Circuit Type Gauges Description Notes
A 95 Initiating Device Circuit (IDC) 18 AWG to 12 AWG TFN/THHN, FPLR, FPL, FPLP
Input circuits on 3-IDC8/4 and modules
(CT1, CT2, WTM, MM, UM & MAB)
B 95
Notification Appliance Circuit (NAC)
24 Vdc
18 AWG to 12 AWG TFN/THHN, FPLR, FPL, FPLP
Output Circuits on ZA8-2 and modules
(CC1, CC2, UM, & MAB)
C 95 Notification Appliance (NAC) Audio 18 AWG to 12 AWG Twisted Pair - FPLR, FPL, FPLP 3-ZAxx to CC1 & CC2 & speakers
D 95 Signature Analog Addressable Loop 18 AWG to 12 AWG TFN/THHN, FPLR, FPL, FPLP Loop Controller (3-SSDC) to Signature devices.
E 95 Analog Addressable Loop 18 AWG to 12 AWG TFN/THHN, FPLR, FPL, FPLP 3-AADC to Addressable devices (not Signature)
H 96 Firemen's Telephone 18 AWGt o 12 AWG 1 Pair Twisted Shielded 3-ASU to CC1, CC1 to Jack/Station.
I 95 24 Vdc Power distribution 18 AWG to 12 AWG TFN/THHN, FPLR, FPL, FPLP 4 Wire Detector/Relay/Annc. AWG depends on voltage drop
K 97 Security (3-SAC) Bus 18 AWG to 14 AWG FPLR, FPL, FPLP 3-SAC to CRC & KPDISP.
L 96 Card/PIN Reader 22 AWG to 16 AWG FPLR, FPL, FPLP or CM, CMR, CMP CRC to Card/PIN Reader.
M 96 Security Device Circuit 22 AWG to 16 AWG FPLR, FPL, FPLP or CM, CMR, CMP CRC or SEC-2 to Door Contact/ Request to Exit.
N 95 Relay Module (FSRRM) 18 AWG to 12 AWG TFN/THHN, FPL, FPLR, FPLP
Five dry contact relays.
Form C Configurable as zone or common
R - CO Telephone Line
Supplied with
3-Modcom
Supplied with 3-Modcom
3-Modcom to RJ31X, 7 feet, plug to plug,
cable EST P/N 3601377.
S 99
RS-232Communications
Printer/Fireworks
22 or 18 AWG
4 cond. min.
FPLR, FPL, FPLP or CM, CMR, CMP
50 feet Max. Panel to Printer or from Panel
to Fireworks
T 98 Audio Network 18 AWG to 12 AWG FPLR FPL, FPLP 5000 feet max between any three panels.
U 98 RS-485 Communications Network 18 AWG to 12 AWG FPLR, FPL, FPLP 5000 feet max between any 3 panels.
W 100 Network Fiber Optics
9/125 Singlemode
62.5/125 mm or
100/140 mm Multimode
OFNR, OFNP Fiber Optic (3-FIB) card
X 100 Netcom-16D Router Cable (Ethernet) CAT 5E/6 CMR, CMP, CMG. CM Cable from Fireworks to NETCOM-16D (300Ft. Max)
Y 100
Fireworks Short Haul Modems
(FW-XPC/FW-XPL)
26 AWG Min.
(4 Conductor)
Twisted Pairs
Telephone cable
Cable for Modem to Modem connections
(FW-XPC/FW-XPL)
For maximum wire lengths consult the reference section. For more detail on wiring specifications refer to the product manuals and installation sheets for the specific product.