Specifications
18
Diagrams are for reference only.
Consult the appropriate installation sheet for wiring details.
TM
CONTROL PANELS
CIRCUIT REFERENCE TABLE - QUICKSTART (QS1, QS4, QSC)CIRCUIT REFERENCE TABLE - QUICKSTART (QS1, QS4, QSC)
CIRCUIT REFERENCE TABLE - QUICKSTART (QS1, QS4, QSC)CIRCUIT REFERENCE TABLE - QUICKSTART (QS1, QS4, QSC)
CIRCUIT REFERENCE TABLE - QUICKSTART (QS1, QS4, QSC)
For cable part numbers turn to the Paige/EST Cross Reference Table on the page indicated
Ref/Pg
Circuit Type Gauges Description Notes
A 95
Initiating Device Circuit
(IDC)
18 AWG to 12 AWG
TFN, THHN, FPL, FPLR,
FPLP
Input circuits on ZB16-4, ZA8-2 and
modules (CT1, CT2, WTM, MM, UM & MAB)
B 95
Notification Appliance
Circuit (NAC) 24 Vdc
18 AWG to 12 AWG
TFN, THHN, FPL, FPLR,
FPLP
Output Circuits on SLIC, ZB16-4, ZA8-2,
and modules (CC1, CC2, UM, & MAB)
D 95 Signature Addressable Loop 18 AWG to 12 AWG
TFN, THHN, FPL, FPLR,
FPLP
Loop Controller (SLIC) card to
addressable devices
I 95
24 Vdc Power distribution
(Smoke Acc. & AUX Power)
18 AWG to 12 AWG
TFN, THHN, FPL, FPLR,
FPLP
4 Wire Detector/Relay/Annc.
AWG depends on voltage drop
N 95 Relay Module (ZR8) 18 AWG to 12 AWG
TFN, THHN, FPL, FPLR,
FPLP
Eight dry contact relays (ZR8)
Form A or B configurable.
R -
Telephone Line - DACT
connection to RJ31X jack
7 ft cable supplied with FSDACT supplied with DACT Terminal to Plug cable
S 99
RS-232 Communications
(Printer Wiring)
18 AWG 4 cond. min. FPL, FPLR, FPLP 50 Ft Max. Panel to Printer
U 98
Communications
Network RS-485
18 AWG to 12 AWG FPL, FPLR, FPLP
Annunciator to Panel and Network
Annunciator
For maximum wire lengths see the tables, formulas and matrix in the reference section.