Specifications
9
TM
Diagrams are for reference only.
Consult the appropriate installation sheet for wiring details.
CONTROL PANELS
CIRCUIT REFERENCE TABLE - FIRESHIELDCIRCUIT REFERENCE TABLE - FIRESHIELD
CIRCUIT REFERENCE TABLE - FIRESHIELDCIRCUIT REFERENCE TABLE - FIRESHIELD
CIRCUIT REFERENCE TABLE - FIRESHIELD
Circuit Reference Table - FireShield
Ref/Pg
Circuit Type Gauges Description Notes
A
95
Initiating Device Circuit (IDC) 18 AWG to 12AWG
TFN, THHN, FPL,
FPLR, FPLP
Alarm, Waterflow, Supervisory &
Monitor circuits
B
95
Notification Appliance Circuit
(NAC) 24 VDC
18 AWG to 12AWG
TFN, THHN, FPL,
FPLR, FPLP
Horns & Strobe circuits
I
95
24 VDC Power distribution
(Aux)
18 AWG to 12AWG
TFN, THHN, FPL,
FPLR, FPLP
Power for 4 Wire Detector, Relay,
FSRSI, FSRZI-A, FSRRM.
AWG depends on voltage drop
N
95
Relay Module (FSRRM) 18 AWG to 12 AWG
TFN, THHN, FPL,
FPLR, FPLP
Five dry contact relays. Form C
configurable as zone or common
R -
Telephone Line - DACT
connection to RJ31X jack
7 ft long cable supplied with FSDACT Plug to plug cable
V 99
Serial Communication Bus for
remote annunciator & relays
18 AWG to 12AWG FPL, FPLR, FPLP
Wiring for the FSRSI,
FSRZI-A or FSRRM.
For maximum wire lengths see the tables, formulas and matrix in the reference section.
For more detail on wiring specifications refer to the product manuals and installation sheets for the specific product.
For cable part numbers turn to the Paige / EST Cross Reference Table on the page indicated.