About This Manual
This manual is intended as a complete guide to the 4 zone conventional Surveyor ENVOY MINI 4 fire
alarm control panel. Installation and commissioning instructions are provided in the first part of the
manual with the following sections dealing with technical details and operation. A separate Log Book is
also provided.
System Design and Planning
It is assumed that the system, of which this control panel is a part, has been designed by a competent
fire alarm system designer in accordance with BS 5839 Part 1: 1988 (from 15th July 2003 this will be
BS5839 Part 1: 2002) and with regard to BS EN 54 parts 2 and 4 in the case of control equipment and
power supplies. Design drawings should be provided to clearly show the position of any field devices
and ancillary equipment.
Panel Types
FCPENV-MINI 4 – A four zone, non extendable control panel with an integral 1.0 Amp PSU and
space for 2 x 12V S.L.A batteries. Cabinet size: 277mm Wide x 200mm High x 97mm Deep
General
The control panel is a micro-processor controlled, conventional fire alarm control system, comprising of
one circuit board. The enclosure consists of back box and hinged, removable lid. Constructed of 1.2mm
(18swg) zintec mild steel and powder coated in textured light grey. The enclosure is designed to give
protection to IP30 level (for indoor use only)
The control panel is available as a 4 zone only and has no provision for repeater panels.
These panels are designed to comply with the requirements of BS EN 54 part 2 1998, but include
integral facilities to enable connection to older systems, which may not comply with current standards.
The control panels are compatible with a wide range of detection and alarm devices. Refer to technical
specification for details. The ENVOY MINI4 control panel has integral detector removal monitoring and
no special active end of line units are required.
ENVOY MINI4 control panels are simple to install and operate. Control functions are enabled by code
entry. The panel fascia is retained by a security cam lock . No internal access is required under normal
usage.
Equipment guarantee
This equipment is not guaranteed unless the complete system is installed and commissioned in accordance
with the laid down national standards by an approved and competent person or organisation.
This product has been manufactured in conformance with the requirements of all applicable
EU Council Directives.