Technical data

MENV-MINI4-02 Issue2 June 2006
22
Disable Zones or Sounders
DISABLE ZONES
To disable / isolate zones , enter code to activate controls and press the DISABLE button on the
keypad Now use buttons 1 – 4 to select which zone(s) to disable and then press ENTER when all
selections have been made. The disable mode will “time out” within 5 seconds if the ENTER button is
not pressed. It is possible to select any, or all zones, to be isolated at the same time. The disabled LED
will be illuminated. The fault LED of the zone that is disabled will be illuminated and the internal buzzer
will be sounding.
DISABLE SOUNDERS
To disable sounder circuits press the SOUND ALARMS button instead of buttons 1 – 4 (see above)
and then press ENTER. The sounder fault LED and the disabled LED will be illuminated.
To ‘enable’ the zones or sounder circuits again, simply repeat exactly the same procedure. WARNING
zones and sounder circuits that have been disabled cannot be enabled by the use of the RESET
button.
Remember to push each button slowly and deliberately. There is a half second delay on the
buttons to prevent misuse. The panel will bleep to acknowledge each push of the button.