Technical data
MENV-MINI4-02 Issue2 June 2006
16
SECTION 6 – TECHNICAL DATA
• Mains input voltage ; 230Vac, 50-60 Hz (Harmonised) +10% to -15% compliant with BSEN54
Pt4 : 1997 for fire alarm power supplies.
• Nominal system voltage 24V dc.
• Power supply : Current limited 1amp suits SLA batteries only. Charging voltage 27.6 volts +/-
0.2V
• Temperature range: -5 to +40
o
C. Maximum relative humidity = 95%.
GENERAL DATA & CURRENT CONSUMPTION FIGURES
BATTERY SIZES
The panel has space for the following batteries, based on standard sizes as supplied by the
manufacturer.
Part No Zones Description Qty
Conventional
Sndr ccts
Total
Sndr
Load
(Amps)
Quiesce
nt
Current
Panel
Only in
Alarm
FCPENV-MINI4 4 Compact non extendable 2 1 57mA 100mA
Part No. Batteries
FCPENV-MINI4
Cabinet Size: 277W x 200H x 97D mm
2 x 1.2Ah 12 Volt SLA
2 x 2.0Ah 12 Volt SLA
2 x 4.5Ah 12 Volt SLA
Detector Zones:
Voltage 17 – 28V dc. Quiescent current 3.5mA each. End of line value 4K7 Ohm.
Schottky diode or zenner clamp detector removal monitoring.
Sounder Cicuits:
17 – 28V dc reverse polarity monitored. Sounders must be polarised and
suppressed. End of line value 4K7 Ohm. Output current 500mA. Maximum shared
sounder load 1.0 amp.
Fuses:
Mains: F 2A H, 250vac, 20mm HBC ceramic. Compliant with IEC (EN60127 Pt.2)
Battery: 1 amp, nanofuse, fast acting
Supply: 1 amp, nanofuse, fast acting
Sounders: 500mA, nanofuse, fast acting