Technical data

MENV-MINI4-02 Issue2 June 2006
14
SECTION 5 – FAULT FINDING
General
A fault is indicated by the illumination of the SYSTEM FAULT LEDs and a buzzer tone. Specific faults
are identified by additional fascia indicators, e.g. zone fault. The buzzer tone varies depending on the
fault and may, or may not, be silenceable.
Fault Latch
If an intermittent fault exists, it is possible to make all fault indications latch, to help identify problems. To
activate fault latch, select option DIL switch 1 to ON.
Zone Fault Indications
Identify the nature of the zone fault with the following method. When a zone fault is present:
Press and hold:
Button 1 to identify open circuit fault
Button 2 to identify short circuit fault
Button 3 to identify detector removed fault
If the zone fault indication remains when any of the buttons are pressed then that is the fault identified. If
the indication clears when the button is pressed then that fault is not present.
Steady zone fault LED = Zone in test or disabled
Pulsing zone fault LED = Zone in fault condition